Fluid-components-international FLT93 Nuclear Manuel d'utilisateur Page 28

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 58
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 27
OPERATION FLT
®
Series FlexSwitch
TM
28 Fluid Components International LLC
Note: The alarm can be set for a specifi c fl ow rate. Follow the Air/Gas Flow Application procedure up to step 7 except establish the
specifi c fl ow rate rather than the normal fl ow. The output signal will be the set point value. Determine whether the alarm
should actuate with decreasing or increasing fl ow and skip to the appropriate step 4 in Detecting Decreasing Flow or Detect-
ing Increasing Flow, respectfully. Enter the specifi c fl ow rate value as the set point. Then follow the Continue With the Air /
Gas Flow Procedure steps.
The relay logic default confi guration is set for the relay coil to be de-energized when the fl ow signal voltage is greater than
the set point value. (i.e., Assume that the normal process fl ow condition has been established. In this state, the relay coil
will be energized if the alarm has been set for low-fl ow detection and de-energized if the alarm has been set for high fl ow
detection.) A recommendation is to have the relay coils energized when the process condition is normal. This will enable the
alarm to close or open the contacts in case of a power failure.
Adjustment by Observation
Note: The control circuit has two mutually exclusive alarms; they are identifi ed as Alarm No. 1 and Alarm No. 2 and each has a set
point adjustment potentiometer and LED indicator. Each alarm can be setup for one of three applications: fl ow, level/inter-
face, or temperature. The following application specifi c adjustment procedures are generic and can be used for setting either
or both alarms. The mode switch must be in the RUN position. Use Figure 3-2 to help locate the adjustment potentiometers
and LEDs.
Flow Applications
1. Ensure that the instrument has been properly installed in the pipeline. Fill the pipeline so the sensing element is surrounded by the
process medium.
2. Apply power to the instrument and allow fi fteen minutes for the sensing element to become active and stabilize.
3. Flow the pipeline at the normal or expected rate. Remove the enclosure cover to allow access to the control circuit to make adjustments.
Detecting Decreasing Flow (low fl ow alarm)
If the status LED is off, turn the set point adjustment potentiometer clockwise until the LED turns on. With the LED on, slowly turn the po-
tentiometer counterclockwise one turn past the point at which the LED just turns off. The potentiometer may have up to one-quarter turn of
hysteresis, therefore, if the mark is overshot, the procedure should be repeated.
Detecting Increasing Flow (high fl ow alarm)
If the status LED is on, turn the set point adjustment potentiometer counterclockwise until the LED turns off. With the LED off, slowly turn the
potentiometer clockwise one-half turn past the point at which the LED just turns on. The potentiometer may have up to one-quarter turn of
hysteresis, therefore, if the mark is overshot, the procedure should be repeated.
Signal Output for Flow Applications
The output signal at connector P1 varies inversely with fl ow rate. The output signal level is also relative to the type of process media, see
Figure 3-3.
Level Applications
1. Ensure that the instrument has been properly installed in the vessel.
2. Apply power to the instrument and allow fi fteen minutes for the sensing element to become active and stabilize.
3. Remove the enclosure cover to allow access to the control circuit to make adjustments.
Detecting Dry Condition (adjustment with sensing element wet)
Verify that the sensing element is wet. If the status LED is off, turn the set point adjustment potentiometer clockwise until the LED turns on.
With the LED on, slowly turn the potentiometer counterclockwise one turn past the point at which the LED just turns off. The potentiometer
may have up to one-quarter turn of hystereses, therefore, if the mark is overshot, the procedure should be repeated.
Vue de la page 27
1 2 ... 23 24 25 26 27 28 29 30 31 32 33 ... 57 58

Commentaires sur ces manuels

Pas de commentaire