INSTALLATION FLT
®
Series FlexSwitch
TM
14 Fluid Components International LLC
Install and Wire the Enclosure(s)
Caution:
In applications where the sensing element is located in an explosive environment, isolate the conduit before it leaves the
environment. A potting Y may be used to provide the isolation.
Pulling wires can cause damage to the control circuit. Therefore, remove the control circuit from the enclosure and use
extreme care when pulling wires into the enclosure.
Mount and wire the control circuit either locally or remotely (option) by following the local or remote enclosure procedure below.
Minimum Wire Size
Table 2-1 shows the smallest (maximum AWG number) copper wire that is used in the electrical cables. Use a lower gauge of wire for less of
a voltage drop. Contact FCI concerning greater distances than those listed in the table. The sensing element cable must be shielded. If the
cable is spliced the shield wire must be continued through the splice. If a terminal block is used, the shield must have its own terminal.
Enclosures Covers
All enclosure covers must be in place and securely closed to achieve environmental and safety classifi cations.
All circular thread-on covers should be tightened about 1/3-turn past hand tight.
Cover locks must be in place and secure if required by a particular approval.
Note: Nitrile (buna-N) O-rings are standard on the circular thread covers;n these O-rings have a 250°F (121°C) maximum useage
temperature.
A Viton O-ring [400°F (204°C) max. temp.] is available for the thread-on covers; these O-rings have a 500°F (260°C) maximum useage tem-
perature.
To receive a Viton O-ring, provide FCI with the following information:
• Shipping address
• Quantity required
• Desired P/N:
Use P/N 000391-01 for the single conduit port enclosure (Local)
Cable and Conduit Entry Devices
The cable and conduit entry devices and blanking elements shall be of a certifi ed fl ameproof type EEx d, suitable for the conditions of use and
correctly installed. With the use of conduit entries a ceiling device shall be provided immediately on the entrance of the device.
All cable glands and conduit fi ttings, includign conduit plugs, must meet or exceed the area approval where the unit is being installed.
Connection
Maximum Distance for AWG
10 ft.
(3m)
50 ft
(15m)
100 ft.
(31m)
250 ft.
(76m)
500 ft.
(152m)
1000 ft.
(305m)
AC/DC Power 22 22 22 20 18 16
Relay (6A) 28 22 20 16 12 10
Flow Element Wires* 22 20 20 18 18 18
* Requires a shielded cable with the shield wire connected to the control socket only.
Table 2-1 Maximum AWG Number